Filter Housings - Velcon Filters
Filter Housings - Velcon Filters
Filter Housings - Velcon Filters
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
<strong>Filter</strong> <strong>Housings</strong><br />
VF-61, VF-61E, VF-62<br />
Clean Dry Fuels and Oils with<br />
High Performance Aquacon ® <strong>Filter</strong> Cartridges<br />
FEATURES<br />
• Free and emulsified water to less than 5 ppm<br />
• 1/2 micrometer particulate removal<br />
• Provides protection against “slugs” of water<br />
• Pressure increase signals cartridge change<br />
• Use with existing filter housings<br />
DESCRIPTION<br />
The VF-61, and VF-62 are versatile filter housings<br />
designed for use with several different high performance<br />
Aquacon filter cartridges, as well as a variety of paper<br />
filters and coalescer/separator cartridges. Refer to the<br />
cartridge selection table on page 3.<br />
Aquacon cartridges filter out water by chemically locking<br />
it into layers of super-absorbent media. Water removal<br />
efficiency is not affected by common surfactants or<br />
additives. Water capacity is as much as 1 1 /2 quarts,<br />
depending on the flow rate. These cartridges also<br />
effectively filter out dirt, rust and other particulates.<br />
(See caution, page 4)<br />
As a cartridge reaches its water-holding limit, the media<br />
expands very rapidly and restricts the flow. For oils and<br />
other high viscosity liquids, the pressure drop will rapidly<br />
increase, signaling the need to change cartridges.<br />
The VF-61, with ACO series cartridges installed, has<br />
become the standard for low flow rate full flow aviation<br />
fuel monitor applications.<br />
Use the VF-61E with band clamp closure for areas with<br />
limited space.<br />
APPLICATIONS<br />
Jet Fuel<br />
Avgas<br />
Motor Gasoline<br />
Diesel Fuel<br />
Biodiesel Fuel<br />
Insulating Oil<br />
Hydraulic Oil<br />
Lubricating Oil<br />
Selected Solvents<br />
VF-61<br />
VF-61E<br />
with Band Clamp Closure<br />
VF-62<br />
Pictured with Optional<br />
Hand Knobs<br />
© 2011 <strong>Velcon</strong> <strong>Filter</strong>s, LLC. 2105-R1 10/11
DIMENSIONAL DRAWINGS<br />
Please note: Drawings are not to scale. Dimensions are shown for estimating purposes only.<br />
Allow 6 inches (15.2 cm) below the vessel to safely remove the vessel to gain access to the cartridge.<br />
5-7/16”<br />
(13.8cm)<br />
VF-61<br />
Bolts<br />
8-1/2”<br />
(22.2cm)<br />
3”<br />
(7.6cm)<br />
5-7/16”<br />
(13.8cm)<br />
VF-61E<br />
Clamp<br />
7-1/2”<br />
(19cm)<br />
3”<br />
(7.6cm)<br />
13/32” Dia<br />
(typ.)<br />
1-1/2” NPT<br />
13/32” Dia<br />
(typ.)<br />
20”<br />
(50.8cm)<br />
6”<br />
(15cm)<br />
Optional CK-1488 Handles<br />
When assembled, the outside<br />
length becomes 10” (25.4cm)<br />
1/8”NPT<br />
Vent x3<br />
20”<br />
(50.8cm)<br />
6”<br />
(15cm)<br />
1-1/2” NPT<br />
1/8”NPT<br />
Vent x3<br />
1/2” NPT<br />
Drain<br />
1/2” NPT<br />
Drain<br />
VF-61E has a band clamp closure. Use in<br />
areas with limited space.<br />
5-7/16”<br />
(13.8cm)<br />
VF-62<br />
Bolts<br />
8-1/2”<br />
(22.2cm)<br />
3”<br />
(7.6cm)<br />
13/32” Dia<br />
(typ.)<br />
1-1/2” NPT<br />
32-1/2”<br />
(81.92cm)<br />
6”<br />
(15cm)<br />
Optional CK-1488 Handles<br />
When assembled, the outside<br />
length becomes 10” (25.4cm)<br />
1/8”NPT<br />
Vent x3<br />
1/2” NPT<br />
Drain<br />
VF-62 has a longer body for areas and<br />
applications that require higher flow rate.
FILTER CARTRIDGE SELECTION TABLE<br />
Housing<br />
P/N<br />
VF-61,<br />
VF-61E<br />
VF-62<br />
Product<br />
being filtered<br />
Jet Fuel &<br />
Avgas (1)<br />
Application<br />
Cartridge<br />
P/N<br />
Data<br />
Sheet<br />
Type Micron<br />
ACO-512P3L<br />
Aquacon<br />
1681<br />
® 0.3 5-50<br />
ACO-51201L (Absorbent) 0.5 5-50<br />
OS-51288 1858<br />
Coalescer/<br />
Separator<br />
Flow Rate<br />
(GPM)<br />
Mo-gas AC-51205 1582 Aquacon ® 5 5-50<br />
AD-51225 1655 (Absorbent) 25 15-50<br />
Dirt & Free<br />
Diesel (1) water<br />
Coalescer/<br />
OS-51286 2118<br />
5 5-18<br />
Separator<br />
Biodiesel AD-51225 1655<br />
Aquacon ®<br />
(Absorbent)<br />
0.5<br />
25 15-50<br />
Jet: 5-35<br />
Avgas: 5-45<br />
AC-51205 1582<br />
5 Varies with oil<br />
Oils<br />
Aquacon<br />
AD-51225 1655 ®<br />
25 viscosity (2)<br />
(Absorbent)<br />
Solvents ASL-51201 1692 1 5-50<br />
ALL<br />
Jet Fuel &<br />
Avgas (1)<br />
Motor<br />
Gasoline<br />
Dirt<br />
FO-512PL1/2<br />
FO-512PL05 1549 Paper <strong>Filter</strong> 5<br />
0.5<br />
FO-512PL25 25<br />
FOS-512PL25 1734 Synthetic <strong>Filter</strong> 25<br />
ACO-52401L 1681<br />
0.5 10-100<br />
AC-52405 1582 5 10-100<br />
Fuels: 5-50<br />
Oils: Varies with<br />
oil viscosity (3)<br />
Diesel (1) Dirt & Free AD-52425 1655 Aquacon ® 25 30-100<br />
Biodiesel<br />
water<br />
(Absorbent)<br />
AC-52405 1582 5<br />
Varies with<br />
viscosity<br />
Oils<br />
See Form<br />
AD-52425 1655 25<br />
#1709<br />
Solvents ASL-52401 1692 1 10-100<br />
ALL<br />
Dirt<br />
FO-524PL1/2<br />
FO-524PL05 1549 Paper <strong>Filter</strong> 5<br />
0.5<br />
FO-524PL25 25<br />
2-100<br />
NOTES:<br />
(1) For aviation and diesel fuel applications, always install a differential pressure gauge or other means of determining<br />
differential pressure.<br />
(2) See Data Sheet #1709 for absorbent cartridge (AC, AD) flow rates.<br />
(3) See Data Sheet # 1532 for paper filter (FO) flow rates, see Data Sheet # 1747 for synthetic filter (FOS) flow rates.<br />
Please consult installation instructions and operating procedures that accompany products for more<br />
detailed information.
SPECIFICATIONS<br />
<strong>Filter</strong> Housing VF-61, VF-61E, VF-62<br />
• Maximum Operating Pressure: 150 psi<br />
• Inlet/Outlet Connection: 1½” NPT<br />
• Closure Seal: Buna-N O-Ring (P/N G-0986)<br />
• ⅛” brass petcock vent valve and ½” drain valve<br />
• Material:<br />
»»<br />
VF-61, VF-62: Die cast aluminum head and<br />
closure clamp assembly; carbon steel shell with<br />
epoxy coated exterior and interior.<br />
»»<br />
VF-61E: Die cast aluminum head; stainless<br />
steel band clamp; carbon steel shell with epoxy<br />
coated exterior and interior.<br />
• Weight:<br />
»»<br />
VF-61: 10 lbs., Shipping Weight: 12lbs.<br />
»»<br />
VF-61E: 8 lbs., Shipping Weight: 10 lbs.<br />
»»<br />
VF-62: 16 lbs., Shipping Weight: 18 lbs.<br />
Cartridges<br />
• Maximum Operating Temperature: 200°F<br />
• Collapse Strength: 75 psi (5 bar)<br />
• pH Range: 5 - 9<br />
• Nominal Filtration Efficiency: 98%<br />
OPTIONS<br />
• Part Number 554Y020 is a Carbon Steel 1 /2” NPT<br />
Ball Valve, with Mounting Nipple<br />
• Part Number CK-1488 quick release hand bolts<br />
(set of 4) to replace closure bolts (as shown on<br />
page 2) VF-61 and VF-62 only.<br />
• Part Number 10678 Differential Pressure Gauge<br />
Assembly (See Form #1959)<br />
DIFFERENTIAL PRESSURE GAUGE<br />
Color Indicates<br />
Pressure Drop<br />
Green: Clean 0 - 15 psi<br />
Red: Change 16 - 25 psi<br />
ORDERING INFORMATION<br />
• Specify Model VF-61, VF-61E, or VF-62 <strong>Filter</strong><br />
Housing<br />
• Unit is supplied with G-0986 Buna-N O-Ring and<br />
1<br />
/8” valve and 1 /2” drain plug installed. 1 /2” petcock<br />
drain valve is shipped loose.<br />
• Cartridges are not supplied and must be ordered<br />
separately.<br />
• Viton O-Rings (P/N G-0986A) are available but must<br />
be ordered separately. They are recommended for<br />
gasoline and solvent applications.<br />
RECOMMENDED SPARES<br />
• 1 each G-0986 Buna-N O-Ring<br />
• If Viton O-Rings are desired, 2 each G-0986A<br />
• 6 each Cartridges<br />
P/N 10678<br />
OVER PRESSURE PROTECTION<br />
When exposed to a high concentration of water, the<br />
differential pressure across an absorbent cartridge (AC,<br />
ACO, AD, or ASL Series cartridges) will immediately<br />
increase. Pressure bypasses or other means to limit the<br />
inlet pressure to 75 psi (5 bar) should be installed to prevent<br />
cartridge from collapsing.<br />
CAUTION<br />
To protect the fuel system, including the filter<br />
housing & other components, be sure to install<br />
pressure relief valve(s).<br />
CAUTION<br />
Do not use Aquacon ® absorbent cartridges (AC, ACO,<br />
AD or ASL Series) with pre-mixed jet fuel containing<br />
anti-icing additives, or with gasoline/alcohol blends.<br />
<strong>Velcon</strong> products are sold and serviced by a world-wide representative<br />
network. To order, contact Headquarters or your LOCAL REPRESENTATIVE:<br />
Due to <strong>Velcon</strong> <strong>Filter</strong>s’ continuing product improvement, drawings, specifications and pictures are subject to change without notice.<br />
COMPANY HEADQUARTERS:<br />
<strong>Velcon</strong> <strong>Filter</strong>s, LLC<br />
1210 Garden of the Gods Road<br />
Colorado Springs, CO 80907-3410<br />
Phone: 1.800.531.0180 / 1.719.531.5855<br />
Fax: 719.531.5690<br />
e-mail: vfsales@velcon.com<br />
www.velcon.com<br />
MANUFACTURING PLANTS LOCATED AT:<br />
Colorado Springs, Colorado<br />
Sylacauga, Alabama<br />
Henryetta, Oklahoma<br />
OFFICES AND AFFILIATES IN:<br />
Canada, Germany, Singapore, & Spain<br />
Liquid Filtration<br />
and Separation<br />
Specialists